DENR Bar
Environmental Fines -- Underground Storage Tank (UST) Section (Division of Waste Management)


Civil Penalties Assessed During the Month of August 2004
Responsible Party
Facility Name
Violation(s)
Penalty Amount
Date Assessed
Stallings Brothers, Inc.
P.O. Box 40
Middlesex, NC

Nash Co.

Kountry Kwik Pik
10762 Liles Rd.
Bailey, NC

Nash Co.

Violation of 15A NCAC 2N .0301 by failing to demonstrate compliance with corrosion protection requirements for 6 UST systems and by failing to demonstrate compliance with overfill control requirements for 3 USTs, violation of 15A NCAC 2N .0304 by failing to provide secondary containment or enhanced leak detection for 6 UST systems located between 100 and 500 feet of a well serving a public water system, violation of 15A NCAC 2N .0502 by failing to meet leak detection requirements for 2 suction piping systems, and violation of 15A NCAC 2N .0506 by failing to maintain records demonstrating compliance with leak detection requirements for 4 pressurized piping systems. $11,845.16 8/30/04
Stallings Brothers, Inc.
P.O. Box 40
Middlesex, NC

Nash Co.

Stallings Bros Coastal
11471 W. Finch Ave.
Middlesex, NC

Nash Co.

Violation of 15A NCAC 2N .0301 and .0302 by failing to demonstrate compliance with corrosion protection requirements for 7 UST systems, violation of 15A NCAC 2N .0502 by failing to meet leak detection requirements for 2 suction piping systems, violation of 15A NCAC 2N .0504 by failing to provide one valid 0.2 gallon per hour leak rate test using an automatic tank gauge at least every 30 days for one UST, and violation of 15A NCAC 2N .0506 by failing to maintain records demonstrating compliance with leak detection requirements for 5 pressurized piping systems. $8,045.16 8/30/04
Quality Oil Company, LLC
1540 Silas Creek Pkwy.
Winston Salem, NC

Forsyth Co.

Bixby Convenience Store
2216 Comatzer Rd.
Advance, NC

Davie Co.

Violation of 15A NCAC 2N .0301 by failing to provide a method of overfill control for 2 USTs. $2,952.70 8/12/04
Return to NOV-UST page